XUPS-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
TimeTicks, Gauge32, Counter32, Integer32
|
|
FROM SNMPv2-SMI
|
|
DisplayString
|
|
FROM SNMPv2-TC
|
|
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE
|
|
FROM SNMPv2-SMI
|
|
MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP
|
|
FROM SNMPv2-CONF
|
|
sysName
|
|
FROM RFC1213-MIB
|
|
eaton, xupsEnvironment
|
|
FROM EATON-OIDS
|
|
-- Need to import these EMP objects to support PowerMIB-style traps for EMP
|
|
xupsContactIndex, xupsContactType, xupsContactState, xupsContactDescr,
|
|
xupsEnvRemoteTemp, xupsEnvRemoteTempLowerLimit, xupsEnvRemoteTempUpperLimit,
|
|
xupsEnvRemoteHumidity, xupsEnvRemoteHumidityLowerLimit,
|
|
xupsEnvRemoteHumidityUpperLimit, xupsEnvRemoteCommunicationStatus
|
|
FROM EATON-EMP-MIB;
|
|
|
|
xupsMIB MODULE-IDENTITY
|
|
LAST-UPDATED "202005270000Z"
|
|
ORGANIZATION "Eaton Corporation"
|
|
CONTACT-INFO
|
|
"Eaton Power Quality Technical Support (PQTS) group
|
|
www.eaton.com/powerxpert
|
|
Technical Resource Center phone numbers
|
|
United States: 1.800.843.9433 or 919.870.3028
|
|
Canada: 1.800.461.9166 ext. 260
|
|
All other countries: Call your local service representative."
|
|
DESCRIPTION
|
|
"Defines Eaton's proprietary PowerMIB for UPS and
|
|
related device data.
|
|
|
|
Copyright (C) Exide Electronics 1992-98
|
|
Copyright (C) Powerware Corporation 1999-2004
|
|
Copyright (C) Eaton Corporation (2005-)."
|
|
|
|
REVISION "202005270000Z"
|
|
DESCRIPTION
|
|
"xupsEnvRemoteCommunicationStatus is added, it reports the EMP communication status.
|
|
Add a new value in enum xupsOutputStatus for the case the output is powered but no continuity feature."
|
|
|
|
REVISION "202001230000Z"
|
|
DESCRIPTION
|
|
"xupsInputTable, xupsOutputTable and xupsBypassTable collection are
|
|
completed with the phase to phase voltage measure."
|
|
|
|
REVISION "201909270000Z"
|
|
DESCRIPTION
|
|
"xupsOutputSource data can monitor the ESS mode."
|
|
|
|
REVISION "201909120000Z"
|
|
DESCRIPTION
|
|
"Provide new data that reflects some battery alarm : xupsBatteryFailure,
|
|
xupsBatteryNotPresent, xupsBatteryAged, xupsBatteryLowCapacity."
|
|
|
|
REVISION "201909100000Z"
|
|
DESCRIPTION
|
|
"Change the data xupsBatteryLastReplacedDate to read-only because the card
|
|
sets it automatically when the battery replacement is detected."
|
|
|
|
REVISION "201904120000Z"
|
|
DESCRIPTION
|
|
"Provide the status of the main AC Input in xupsInputStatus.
|
|
Provide the status of the AC Output in xupsOutputStatus and a new trap
|
|
and alarm 'load not protected' in xupsOutputNotProtected."
|
|
|
|
REVISION "201903050000Z"
|
|
DESCRIPTION
|
|
"Provide more UPS identification data as xupsIdentPartNumber and xupsIdentSerialNumber.
|
|
Provide a collection xupsAgent that contains identification data of the card :
|
|
xupsAgentManufacturer, xupsAgentModel, xupsAgentSoftwareVersion, xupsAgentPartNumber,
|
|
xupsAgentSerialNumber"
|
|
|
|
REVISION "201902190000Z"
|
|
DESCRIPTION
|
|
"To ensure consistency whith the measures done on the UPS, the data following are renamed :
|
|
xupsInputAverageCurrent to xupsInputTotalCurrent,
|
|
xupsOutputAverageCurrent to xupsOutputTotalCurrent,
|
|
xupsBypassAverageCurrent to xupsBypassTotalCurrent."
|
|
|
|
REVISION "201809120000Z"
|
|
DESCRIPTION
|
|
"Add new data xupsInputId, xupsInputName, xupsInputCurrentHighPrecision in the table xupsInputTable.
|
|
Add new sub collection xupsInputTotal with xupsInputAverageVoltage, xupsInputAverageCurrent,
|
|
xupsInputTotalWatts, xupsInputTotalVA, xupsInputAveragePowerFactor inside.
|
|
Add new data xupsOutputId, xupsOutputName, xupsOutputCurrentHighPrecision,
|
|
xupsOutputPercentLoad, xupsOutputVA in the table xupsOutputTable.
|
|
Add new sub collection xupsOutputTotal with xupsOutputAverageVoltage, xupsOutputAverageCurrent,
|
|
xupsOutputTotalWatts, xupsOutputTotalVA, xupsOutputAveragePowerFactor inside.
|
|
Add new data xupsBypassId, xupsBypassName, xupsBypassCurrentHighPrecision,
|
|
xupsBypassWatts in the table xupsBypassTable.
|
|
Add new sub collection xupsBypassTotal with xupsBypassTotalAverageVoltage, xupsBypassAverageCurrent,
|
|
xupsBypassTotalWatts, xupsBypassTotalVA, xupsBypassTotalAverageFactor inside."
|
|
|
|
REVISION "201804230000Z"
|
|
DESCRIPTION
|
|
"Add new data xupsTestTrap, xupstdTestTrap that will allow to initiate a
|
|
test trap sent out from the agent to the trap receivers."
|
|
|
|
REVISION "201211261513Z"
|
|
DESCRIPTION
|
|
"Add the identifier of measures xupsInputId, xupsOutputId and xupsBypassId,
|
|
respectively in the table xupsInputTable, xupsOutputTable and xupsBypassTable."
|
|
|
|
REVISION "201204030000Z"
|
|
DESCRIPTION
|
|
"Add new data xupsOutputHourlyPowerUsage, xupsOutputCumulativePowerUsage,
|
|
and xupsOutputCumulativePowerUsageTimer into the collection xupsOutput.
|
|
Add new data xupsRecepHourlyPowerUsage, xupsRecepCumulativePowerUsage,
|
|
and xupsRecepCumulativePowerUsageTimer into the collection xupsRecepTable."
|
|
|
|
REVISION "201102250000Z"
|
|
DESCRIPTION
|
|
"Add new data xupsSwitchable"
|
|
|
|
REVISION "200810020000Z"
|
|
DESCRIPTION
|
|
"Added new values of batteryDisconnected(6), batteryUnderTest(7),
|
|
and checkBattery(8) to xupsBatteryAbmStatus."
|
|
|
|
REVISION "200705030000Z"
|
|
DESCRIPTION
|
|
"Added new value of pxg(5) to xupsSendTrapType
|
|
for Power Xpert Gateway implementations."
|
|
|
|
REVISION "200703130000Z"
|
|
DESCRIPTION
|
|
"Initial SNMPv2-SMI-compliant Version of PowerMIB.
|
|
Incorporates all revisions of the original xups
|
|
MIB file through Version 3.13 21-May-04."
|
|
|
|
::= { eaton 1 }
|
|
|
|
-- xupsMIB { iso org(3) dod(6) internet(1) private(4)
|
|
-- enterprises(1) eaton(534) xupsMIB(1) }
|
|
|
|
|
|
xupsIdent OBJECT IDENTIFIER ::= { xupsMIB 1 }
|
|
xupsBattery OBJECT IDENTIFIER ::= { xupsMIB 2 }
|
|
xupsInput OBJECT IDENTIFIER ::= { xupsMIB 3 }
|
|
xupsOutput OBJECT IDENTIFIER ::= { xupsMIB 4 }
|
|
xupsBypass OBJECT IDENTIFIER ::= { xupsMIB 5 }
|
|
-- xupsEnvironment OBJECT IDENTIFIER ::= { xupsMIB 6 } - defined in EATON-OIDS
|
|
xupsAlarm OBJECT IDENTIFIER ::= { xupsMIB 7 }
|
|
xupsTest OBJECT IDENTIFIER ::= { xupsMIB 8 }
|
|
xupsControl OBJECT IDENTIFIER ::= { xupsMIB 9 }
|
|
xupsConfig OBJECT IDENTIFIER ::= { xupsMIB 10 }
|
|
xupsTrapControl OBJECT IDENTIFIER ::= { xupsMIB 11 }
|
|
xupsRecep OBJECT IDENTIFIER ::= { xupsMIB 12 }
|
|
xupsTopology OBJECT IDENTIFIER ::= { xupsMIB 13 }
|
|
xupsAgent OBJECT IDENTIFIER ::= { xupsMIB 14 }
|
|
|
|
xupsInputTotal OBJECT IDENTIFIER ::= { xupsInput 8 }
|
|
xupsOutputTotal OBJECT IDENTIFIER ::= { xupsOutput 9 }
|
|
xupsBypassTotal OBJECT IDENTIFIER ::= { xupsBypass 4 }
|
|
|
|
--
|
|
-- xupsIdent group:
|
|
--
|
|
xupsIdentManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS Manufacturer Name (e.g. Eaton Corporation)."
|
|
::= { xupsIdent 1}
|
|
|
|
xupsIdentModel OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS Model (e.g. Powerware Plus Model 18)."
|
|
::= {xupsIdent 2}
|
|
|
|
xupsIdentSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The firmware revision level(s) of the UPS microcontroller(s)."
|
|
::= {xupsIdent 3}
|
|
|
|
xupsIdentOemCode OBJECT-TYPE
|
|
SYNTAX Integer32 (0..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A binary code indicating who the UPS was manufactured or labeled for.
|
|
0 or 255 indicates Eaton itself."
|
|
::= {xupsIdent 4}
|
|
|
|
xupsIdentPartNumber OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..31))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The catalog part number of the UPS device."
|
|
::= { xupsIdent 5 }
|
|
|
|
xupsIdentSerialNumber OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..31))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The serial number of the UPS device."
|
|
::= { xupsIdent 6 }
|
|
|
|
|
|
--
|
|
-- xupsBattery group:
|
|
--
|
|
xupsBatTimeRemaining OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery run time in seconds before UPS turns off due
|
|
to low battery."
|
|
::= { xupsBattery 1}
|
|
|
|
xupsBatVoltage OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "Volts DC"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery voltage as reported by the UPS meters."
|
|
::= {xupsBattery 2}
|
|
|
|
xupsBatCurrent OBJECT-TYPE
|
|
SYNTAX Integer32 (-2147483648..2147483647)
|
|
UNITS "Amps DC"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery Current as reported by the UPS metering.
|
|
Current is positive when discharging, negative
|
|
when recharging the battery."
|
|
::= {xupsBattery 3}
|
|
|
|
xupsBatCapacity OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery percent charge."
|
|
::= { xupsBattery 4}
|
|
|
|
xupsBatteryAbmStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
batteryCharging(1),
|
|
batteryDischarging(2),
|
|
batteryFloating(3),
|
|
batteryResting(4),
|
|
unknown(5),
|
|
batteryDisconnected(6),
|
|
batteryUnderTest(7),
|
|
checkBattery(8)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Gives the status of the Advanced Battery Management and Battery state;
|
|
batteryFloating(3) status means that the charger is temporarily
|
|
charging the battery to its float voltage; batteryResting(4) is the
|
|
state when the battery is fully charged and none of the other actions
|
|
(charging/discharging/floating) is being done.
|
|
checkBattery(8) indicates that the Battery state is uncertain
|
|
following a poor battery test result."
|
|
::= { xupsBattery 5}
|
|
|
|
xupsBatteryLastReplacedDate OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..16))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The date when the Batteries in this UPS were last replaced. Free text format,
|
|
so the preferred local date format may be used (MM/DD/YYYY, DD-Mon-YYYY, etc)."
|
|
::= { xupsBattery 6}
|
|
|
|
xupsBatteryFailure OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates if a battery fault detected or battery tests failed."
|
|
::= { xupsBattery 7}
|
|
|
|
xupsBatteryNotPresent OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates if the UPS has no battery either internal or external."
|
|
::= { xupsBattery 8}
|
|
|
|
xupsBatteryAged OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates if the battery is over aged."
|
|
::= { xupsBattery 9}
|
|
|
|
xupsBatteryLowCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(1),
|
|
no(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates if the battery capacity is below the threshold set in the UPS."
|
|
::= { xupsBattery 10}
|
|
|
|
|
|
--
|
|
-- xupsInput group:
|
|
--
|
|
xupsInputFrequency OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "0.1 Hertz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The utility line frequency in tenths of Hz."
|
|
::= {xupsInput 1}
|
|
|
|
xupsInputLineBads OBJECT-TYPE
|
|
SYNTAX Counter32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of times the Input was out of tolerance
|
|
in voltage or frequency."
|
|
::= {xupsInput 2}
|
|
|
|
xupsInputNumPhases OBJECT-TYPE
|
|
SYNTAX Integer32 (0..6)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of input phases (normally 1 to 3)."
|
|
::= {xupsInput 3}
|
|
|
|
xupsInputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF XupsInputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of input table entries. The number of entries
|
|
is given by the value of xupsInputNumPhases."
|
|
::= {xupsInput 4}
|
|
|
|
xupsInputEntry OBJECT-TYPE
|
|
SYNTAX XupsInputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input table entry containing the current,
|
|
voltage, etc. readings for one phase."
|
|
INDEX { xupsInputPhase }
|
|
::= { xupsInputTable 1 }
|
|
|
|
XupsInputEntry ::= SEQUENCE {
|
|
xupsInputPhase Integer32,
|
|
xupsInputVoltage Integer32,
|
|
xupsInputCurrent Integer32,
|
|
xupsInputWatts Integer32,
|
|
xupsInputId INTEGER,
|
|
xupsInputName OCTET STRING,
|
|
xupsInputCurrentHighPrecision Integer32,
|
|
xupsInputVoltagePhaseToPhase Integer32
|
|
}
|
|
|
|
xupsInputPhase OBJECT-TYPE
|
|
SYNTAX Integer32 (0..6)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of the phase. Serves as index for input table."
|
|
::= {xupsInputEntry 1}
|
|
|
|
xupsInputVoltage OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured input voltage from the UPS meters in volts."
|
|
::= {xupsInputEntry 2}
|
|
|
|
xupsInputCurrent OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured input current from the UPS meters in amps."
|
|
::= {xupsInputEntry 3}
|
|
|
|
xupsInputWatts OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured input real power in watts."
|
|
::= {xupsInputEntry 4}
|
|
|
|
xupsInputId OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
phase1toN (1),
|
|
phase2toN (2),
|
|
phase3toN (3),
|
|
phase1to2 (4),
|
|
phase2to3 (5),
|
|
phase3to1 (6)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"value indicates what measurement is being stored in this table row :
|
|
phase1 to neutral, phase2 to neutral, phase3 to neutral,
|
|
phase1 to phase2, phase2 to phase3, phase3 to phase1."
|
|
::= { xupsInputEntry 5 }
|
|
|
|
xupsInputName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..31))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A descriptive name for the phase, example : L1/A for the phase 1."
|
|
::= { xupsInputEntry 6 }
|
|
|
|
xupsInputCurrentHighPrecision OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS tenth of Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured input current from the UPS meters in tenth of amps."
|
|
::= {xupsInputEntry 7}
|
|
|
|
xupsInputVoltagePhaseToPhase OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured input phase to phase voltage from the UPS meters in volts,
|
|
For the phase n, it is the measure of phase n to phase n+1 voltage."
|
|
::= {xupsInputEntry 8}
|
|
|
|
xupsInputSource OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
other(1),
|
|
none(2),
|
|
primaryUtility(3),
|
|
bypassFeed(4),
|
|
secondaryUtility(5),
|
|
generator(6),
|
|
flywheel(7),
|
|
fuelcell(8)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present external source of input power. The enumeration
|
|
'none(2)' indicates that there is no external source of
|
|
power, for example, the UPS is On Battery (an internal source).
|
|
'primaryUtility' indicates the normal case of utility input power.
|
|
The 'bypassFeed' can only be used when the Bypass source is known
|
|
to be a separate utility feed than the primaryUtility(3).
|
|
'secondaryUtility' indicates that a secondary utility feed is supplying
|
|
power (on a dual AC input UPS).
|
|
'generator' indicates that input power is provided by a generator.
|
|
Note that the alternate energy sources of 'flywheel' and 'fuelcell' are
|
|
not necessarily AC input sources."
|
|
::= { xupsInput 5 }
|
|
|
|
-- xupsDualInputStatus and xupsSecondaryInputWatch would only be present
|
|
-- for UPSs with a secondary input source.
|
|
|
|
xupsDualInputStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
bothSourcesBad(1),
|
|
primarySourceGood(2),
|
|
secondarySourceGood(3),
|
|
bothSourcesGood(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present status of the sources of input power in a dual source UPS.
|
|
The enumeration primarySourceGood(2) indicates that the primary source
|
|
of power is present and within 'normal' ranges for voltage and
|
|
frequency, but the secondary source is either not present or not in an
|
|
acceptable range.
|
|
'secondarySourceGood' indicates that only the Secondary power feed is
|
|
available and within its limits.
|
|
The enumeration bothSourcesGood(4) indicates that both sources are present
|
|
and within their respective 'normal' ranges;
|
|
bothSourcesBad(1) indicates that neither source is present, or, if present,
|
|
is not within acceptable ranges.
|
|
This object will only be implemented for UPSs with two sources of input
|
|
power, e.g., redundant AC feeds or a separate Bypass or Generator source.
|
|
The secondary source will not be an AC power source in all cases."
|
|
::= { xupsInput 6 }
|
|
|
|
xupsSecondaryInputWatch OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object enables(2) or disables(1) the alarms and traps related to the
|
|
availability and use of the secondary input of a dual-input UPS
|
|
(i.e., OnAlternatePowerSource and AltPowerNotAvailable).
|
|
To avoid nuisance alarms and traps, this object should be set to
|
|
disabled(1) when the UPS is not wired to a secondary source of power.
|
|
This object will only be implemented for UPSs with two sources of input
|
|
power, i.e., redundant AC feeds or a separate Bypass or Generator source."
|
|
::= { xupsInput 7 }
|
|
|
|
--
|
|
-- xupsInputTotal group:
|
|
--
|
|
xupsInputAverageVoltage OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured input voltage from the UPS meters in volts.
|
|
Related to the phase 1 if the UPS is single phase,
|
|
either it is average of all the simple phase voltage."
|
|
::= {xupsInputTotal 1}
|
|
|
|
xupsInputTotalCurrent OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS tenth of Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured input current from the UPS meters in tenth of amps.
|
|
Related to the phase 1 if the UPS is single phase,
|
|
either it is average of all the simple phase current."
|
|
::= {xupsInputTotal 2}
|
|
|
|
xupsInputTotalWatts OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured input active power in watts.
|
|
Sum of all the simple phase watts."
|
|
::= {xupsInputTotal 3}
|
|
|
|
xupsInputTotalVA OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "VA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured input apparent power in VA.
|
|
Sum of all the simple phase VA."
|
|
::= {xupsInputTotal 4}
|
|
|
|
xupsInputAveragePowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the total power factor of the input in hundredths.
|
|
0.92 would be returned as 92."
|
|
::= { xupsInputTotal 5 }
|
|
|
|
xupsInputStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
inputBad(1),
|
|
inputGood(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present status of the primary AC input of the UPS.
|
|
The enumeration inputGood(2) indicates that the primary source
|
|
of power is present and within 'normal' ranges for voltage and
|
|
frequency.
|
|
inputBad(1) indicates that neither source is present, or, if present,
|
|
is not within acceptable ranges."
|
|
::= { xupsInput 9 }
|
|
|
|
--
|
|
-- xupsOutput group:
|
|
--
|
|
xupsOutputLoad OBJECT-TYPE
|
|
SYNTAX Integer32 (0..200)
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS output load in percent of rated capacity."
|
|
::= {xupsOutput 1}
|
|
|
|
xupsOutputFrequency OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "0.1 Hertz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured UPS output frequency in tenths of Hz."
|
|
::= {xupsOutput 2}
|
|
|
|
xupsOutputNumPhases OBJECT-TYPE
|
|
SYNTAX Integer32 (0..6)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of metered output phases."
|
|
::= {xupsOutput 3}
|
|
|
|
xupsOutputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF XupsOutputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of output table entries. The number of entries
|
|
is given by the value of xupsOutputNumPhases."
|
|
::= {xupsOutput 4}
|
|
|
|
xupsOutputEntry OBJECT-TYPE
|
|
SYNTAX XupsOutputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output Table Entry containing voltage, current, etc."
|
|
INDEX { xupsOutputPhase }
|
|
::= {xupsOutputTable 1}
|
|
|
|
XupsOutputEntry ::= SEQUENCE {
|
|
xupsOutputPhase Integer32,
|
|
xupsOutputVoltage Integer32,
|
|
xupsOutputCurrent Integer32,
|
|
xupsOutputWatts Integer32,
|
|
xupsOutputId INTEGER,
|
|
xupsOutputName OCTET STRING,
|
|
xupsOutputCurrentHighPrecision Integer32,
|
|
xupsOutputPercentLoad Integer32,
|
|
xupsOutputVA Integer32,
|
|
xupsOutputVoltagePhaseToPhase Integer32
|
|
}
|
|
|
|
xupsOutputPhase OBJECT-TYPE
|
|
SYNTAX Integer32 (0..6)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of the phase. Serves as index for output table."
|
|
::= {xupsOutputEntry 1}
|
|
|
|
xupsOutputVoltage OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured output voltage from the UPS metering in volts."
|
|
::= {xupsOutputEntry 2}
|
|
|
|
xupsOutputCurrent OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured UPS output current in amps."
|
|
::= {xupsOutputEntry 3}
|
|
|
|
xupsOutputWatts OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured real output power in watts."
|
|
::= {xupsOutputEntry 4}
|
|
|
|
xupsOutputId OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
phase1toN (1),
|
|
phase2toN (2),
|
|
phase3toN (3),
|
|
phase1to2 (4),
|
|
phase2to3 (5),
|
|
phase3to1 (6)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"value indicates what measurement is being stored in this table row :
|
|
phase1 to neutral, phase2 to neutral, phase3 to neutral,
|
|
phase1 to phase2, phase2 to phase3, phase3 to phase1. "
|
|
::= { xupsOutputEntry 5 }
|
|
|
|
xupsOutputName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..31))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A descriptive name for the phase."
|
|
::= { xupsOutputEntry 6 }
|
|
|
|
xupsOutputCurrentHighPrecision OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS tenth of Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured output current from the UPS meters in tenth of amps."
|
|
::= {xupsOutputEntry 7}
|
|
|
|
xupsOutputPercentLoad OBJECT-TYPE
|
|
SYNTAX Integer32 (0..200)
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The percentage of the UPS power capacity presently
|
|
being used on this output line"
|
|
::= { xupsOutputEntry 8 }
|
|
|
|
xupsOutputVA OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "VA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured apparent output power in VA."
|
|
::= {xupsOutputEntry 9}
|
|
|
|
xupsOutputVoltagePhaseToPhase OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured output phase to phase voltage from the UPS meters in volts,
|
|
For the phase n, it is the measure of phase n to phase n+1 voltage."
|
|
::= {xupsOutputEntry 10}
|
|
|
|
xupsOutputSource OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
other(1),
|
|
none(2),
|
|
normal(3),
|
|
bypass(4),
|
|
battery(5),
|
|
booster(6),
|
|
reducer(7),
|
|
parallelCapacity(8),
|
|
parallelRedundant(9),
|
|
highEfficiencyMode(10),
|
|
maintenanceBypass(11),
|
|
essMode(12)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present source of output power. The enumeration
|
|
none(2) indicates that there is no source of output
|
|
power (and therefore no output power), for example,
|
|
the system has opened the output breaker.
|
|
'normal', 'bypass', and 'battery' indicate those common UPS statuses.
|
|
'booster' and 'reducer' indicate boost or buck operation, for
|
|
line-interactive UPSs only.
|
|
'parallelCapacity' and 'parallelRedundant' indicate a normal parallel
|
|
UPS system, in either Parallel for Capacity or Redundancy configuration.
|
|
'highEfficiencyMode' is normal but enhanced by High Efficiency mode.
|
|
'maintenanceBypass' indicates that the UPS is in Maintenance/Manual
|
|
Bypass mode.
|
|
'essMode' is normal but enhanced by Energy Saver System.
|
|
'other' covers any other, unusual conditions."
|
|
::= { xupsOutput 5 }
|
|
|
|
xupsOutputHourlyPowerUsage OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "Wh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Units are Watt-hours.This is the energy consumed during the last hour."
|
|
::= { xupsOutput 6 }
|
|
|
|
xupsOutputCumulativePowerUsage OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "Wh"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Units are Watt-hours.This is the energy consumed since the last reset.
|
|
This object is writable so that it can be reset to 0.
|
|
When it is written to 0, the xupsOutputCumulativeWhTimer will be reset to 0 as well."
|
|
::= { xupsOutput 7 }
|
|
|
|
xupsOutputCumulativePowerUsageTimer OBJECT-TYPE
|
|
SYNTAX Counter32
|
|
UNITS "Seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds since the cumulative power usage was last reset."
|
|
::= { xupsOutput 8 }
|
|
|
|
--
|
|
-- xupsOutputTotal group:
|
|
--
|
|
xupsOutputAverageVoltage OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured output voltage from the UPS meters in volts.
|
|
Related to the phase 1 if the UPS is single phase,
|
|
either it is average of all the simple phase voltage."
|
|
::= {xupsOutputTotal 1}
|
|
|
|
xupsOutputTotalCurrent OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS tenth of Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured output current from the UPS meters in tenth of amps.
|
|
Related to the phase 1 if the UPS is single phase,
|
|
either it is average of all the simple phase current."
|
|
::= {xupsOutputTotal 2}
|
|
|
|
xupsOutputTotalWatts OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured output active power in watts.
|
|
Sum of all the simple phase watts."
|
|
::= {xupsOutputTotal 3}
|
|
|
|
xupsOutputTotalVA OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "VA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured output apparent power in VA.
|
|
Sum of all the simple phase VA."
|
|
::= {xupsOutputTotal 4}
|
|
|
|
xupsOutputAveragePowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the total power factor of the output in hundredths.
|
|
0.92 would be returned as 92."
|
|
::= { xupsOutputTotal 5 }
|
|
|
|
xupsOutputStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(0),
|
|
outputNotPowered(1),
|
|
outputNotProtected(2),
|
|
outputProtected(3),
|
|
outputPoweredNoContinuity(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present status of the AC output of the UPS.
|
|
The enumeration outputNotPowered(1) indicates that the output is not powered.
|
|
outputNotProtected(2) indicates that the output is powered but not protected,
|
|
due to following reasons : On bypass, battery fault, or UPS internal failure
|
|
that makes the ups will be inoperant in case of AC input failure.
|
|
outputProtected(3) indicates that the output is powered and protected.
|
|
outputPoweredNoContinuity(4) indicates that the output is powered but this
|
|
is a specific configuration of the device where the continuity feature is disabled."
|
|
::= { xupsOutput 10 }
|
|
|
|
|
|
--
|
|
-- xupsBypass group:
|
|
--
|
|
xupsBypassFrequency OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "0.1 Hertz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The bypass frequency in tenths of Hz."
|
|
::= {xupsBypass 1}
|
|
|
|
xupsBypassNumPhases OBJECT-TYPE
|
|
SYNTAX Integer32 (0..6)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of lines in the UPS bypass table."
|
|
::= {xupsBypass 2}
|
|
|
|
xupsBypassTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF XupsBypassEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of bypass table entries. The number of entries
|
|
is given by the value of xupsBypassNumPhases."
|
|
::= {xupsBypass 3}
|
|
|
|
xupsBypassEntry OBJECT-TYPE
|
|
SYNTAX XupsBypassEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bypass Table Entry containing voltage for each phase."
|
|
INDEX { xupsBypassPhase }
|
|
::= {xupsBypassTable 1}
|
|
|
|
XupsBypassEntry ::= SEQUENCE {
|
|
xupsBypassPhase Integer32,
|
|
xupsBypassVoltage Integer32,
|
|
xupsBypassId INTEGER,
|
|
xupsBypassName OCTET STRING,
|
|
xupsBypassCurrentHighPrecision Integer32,
|
|
xupsBypassWatts Integer32,
|
|
xupsBypassVoltagePhaseToPhase Integer32
|
|
}
|
|
|
|
xupsBypassPhase OBJECT-TYPE
|
|
SYNTAX Integer32 (0..6)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Bypass Phase, index for the table."
|
|
::= {xupsBypassEntry 1}
|
|
|
|
xupsBypassVoltage OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured UPS bypass voltage in volts."
|
|
::= {xupsBypassEntry 2}
|
|
|
|
xupsBypassId OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
phase1toN (1),
|
|
phase2toN (2),
|
|
phase3toN (3),
|
|
phase1to2 (4),
|
|
phase2to3 (5),
|
|
phase3to1 (6)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"value indicates what measurement is being stored in this table row :
|
|
phase1 to neutral, phase2 to neutral, phase3 to neutral,
|
|
phase1 to phase2, phase2 to phase3, phase3 to phase1. "
|
|
::= { xupsBypassEntry 3 }
|
|
|
|
xupsBypassName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..31))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A descriptive name for the phase."
|
|
::= { xupsBypassEntry 4 }
|
|
|
|
xupsBypassCurrentHighPrecision OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS tenth of Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured bypass current from the UPS meters in tenth of amps."
|
|
::= {xupsBypassEntry 5}
|
|
|
|
xupsBypassWatts OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured real bypass power in watts."
|
|
::= {xupsBypassEntry 6}
|
|
|
|
xupsBypassVoltagePhaseToPhase OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured bypass phase to phase voltage from the UPS meters in volts,
|
|
For the phase n, it is the measure of phase n to phase n+1 voltage."
|
|
::= {xupsBypassEntry 7}
|
|
|
|
|
|
-- xupsBypassTotal group:
|
|
|
|
xupsBypassAverageVoltage OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured bypass voltage from the UPS meters in volts.
|
|
Related to the phase 1 if the UPS is single phase,
|
|
either it is average of all the simple phase voltage."
|
|
::= {xupsBypassTotal 1}
|
|
|
|
xupsBypassTotalCurrent OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS tenth of Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured bypass current from the UPS meters in tenth of amps.
|
|
Related to the phase 1 if the UPS is single phase,
|
|
either it is average of all the simple phase current."
|
|
::= {xupsBypassTotal 2}
|
|
|
|
xupsBypassTotalWatts OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured bypass active power in watts.
|
|
Sum of all the simple phase watts."
|
|
::= {xupsBypassTotal 3}
|
|
|
|
xupsBypassTotalVA OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "VA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured output apparent power in VA.
|
|
Sum of all the simple phase VA."
|
|
::= {xupsBypassTotal 4}
|
|
|
|
xupsBypassAveragePowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the total power factor of the input in hundredths.
|
|
0.92 would be returned as 92."
|
|
::= { xupsBypassTotal 5 }
|
|
|
|
|
|
--
|
|
-- xupsEnvironment group:
|
|
--
|
|
|
|
xupsEnvAmbientTemp OBJECT-TYPE
|
|
SYNTAX Integer32 (-100..200)
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The reading of the ambient temperature in the vicinity of the
|
|
UPS or SNMP agent."
|
|
::= { xupsEnvironment 1 }
|
|
|
|
xupsEnvAmbientLowerLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (-100..200)
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Lower Limit of the ambient temperature; if xupsEnvAmbientTemp
|
|
falls below this value, the xupsAmbientTempBad alarm will occur."
|
|
::= { xupsEnvironment 2 }
|
|
|
|
xupsEnvAmbientUpperLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (-100..200)
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Upper Limit of the ambient temperature; if xupsEnvAmbientTemp
|
|
rises above this value, the xupsAmbientTempBad alarm will occur.
|
|
This value should be greater than xupsEnvAmbientLowerLimit."
|
|
::= { xupsEnvironment 3 }
|
|
|
|
xupsEnvAmbientHumidity OBJECT-TYPE
|
|
SYNTAX Integer32 (0..100)
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The reading of the ambient humidity in the vicinity of the
|
|
UPS or SNMP agent."
|
|
::= { xupsEnvironment 4 }
|
|
|
|
--
|
|
-- Moved the EMP-based objects,
|
|
-- from xupsEnvRemoteTemp to xupsEnvRemoteCommunicationStatus
|
|
-- ( { xupsEnvironment 5 to 13 }, including xupsContactSenseTable,
|
|
-- to separate file Eaton-EMP-MIB.txt
|
|
--
|
|
|
|
|
|
|
|
--
|
|
-- xupsAlarm group:
|
|
--
|
|
xupsAlarms OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current number of alarm conditions."
|
|
::= {xupsAlarm 1}
|
|
|
|
xupsAlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF XupsAlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of alarm table entries. The number of entries
|
|
is given by the value of xupsAlarms.
|
|
Note that this table is sparsely (non-consecutively)
|
|
numbered and will be empty if there are no active alarms."
|
|
::= {xupsAlarm 2}
|
|
|
|
xupsAlarmEntry OBJECT-TYPE
|
|
SYNTAX XupsAlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Alarm Table Entry containing descriptive information
|
|
for one alarm entry."
|
|
INDEX { xupsAlarmID }
|
|
::= {xupsAlarmTable 1}
|
|
|
|
XupsAlarmEntry ::= SEQUENCE {
|
|
xupsAlarmID Integer32,
|
|
xupsAlarmDescr OBJECT IDENTIFIER,
|
|
xupsAlarmTime TimeTicks
|
|
}
|
|
|
|
xupsAlarmID OBJECT-TYPE
|
|
SYNTAX Integer32 (1..2147483647)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique identifier for an alarm condition."
|
|
::= {xupsAlarmEntry 1}
|
|
|
|
xupsAlarmDescr OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A reference to an alarm description object. The object
|
|
referenced should not be accessible, but rather be used to
|
|
provide a unique description of the alarm condition."
|
|
::= {xupsAlarmEntry 2}
|
|
|
|
xupsAlarmTime OBJECT-TYPE
|
|
SYNTAX TimeTicks
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the MIB-II variable sysUpTime when the alarm
|
|
condition occurred."
|
|
::= {xupsAlarmEntry 3}
|
|
|
|
--
|
|
-- Well known alarm conditions.
|
|
--
|
|
xupsOnBattery OBJECT IDENTIFIER ::= {xupsAlarm 3}
|
|
xupsLowBattery OBJECT IDENTIFIER ::= {xupsAlarm 4}
|
|
xupsUtilityPowerRestored OBJECT IDENTIFIER ::= {xupsAlarm 5}
|
|
xupsReturnFromLowBattery OBJECT IDENTIFIER ::= {xupsAlarm 6}
|
|
xupsOutputOverload OBJECT IDENTIFIER ::= {xupsAlarm 7}
|
|
xupsInternalFailure OBJECT IDENTIFIER ::= {xupsAlarm 8}
|
|
xupsBatteryDischarged OBJECT IDENTIFIER ::= {xupsAlarm 9}
|
|
xupsInverterFailure OBJECT IDENTIFIER ::= {xupsAlarm 10}
|
|
xupsOnBypass OBJECT IDENTIFIER ::= {xupsAlarm 11}
|
|
xupsBypassNotAvailable OBJECT IDENTIFIER ::= {xupsAlarm 12}
|
|
xupsOutputOff OBJECT IDENTIFIER ::= {xupsAlarm 13}
|
|
xupsInputFailure OBJECT IDENTIFIER ::= {xupsAlarm 14}
|
|
xupsBuildingAlarm OBJECT IDENTIFIER ::= {xupsAlarm 15}
|
|
xupsShutdownImminent OBJECT IDENTIFIER ::= {xupsAlarm 16}
|
|
xupsOnInverter OBJECT IDENTIFIER ::= {xupsAlarm 17}
|
|
|
|
|
|
xupsAlarmNumEvents OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of entries in the UPS event history queue."
|
|
::= { xupsAlarm 18 }
|
|
|
|
xupsAlarmEventTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF XupsAlarmEventEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of the UPS internal event history queue."
|
|
::= { xupsAlarm 19 }
|
|
|
|
xupsAlarmEventEntry OBJECT-TYPE
|
|
SYNTAX XupsAlarmEventEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One of the entries in the UPS event history queue."
|
|
INDEX { xupsAlarmEventID }
|
|
::= { xupsAlarmEventTable 1 }
|
|
|
|
-- The first 4 vars in the xAEEntry have been deprecated, since they resulted in
|
|
-- a flood of difficult to interpret data. They have been replaced by the single
|
|
-- entry, xupsAlarmEventMsg, which gives a human-readable description of the event.
|
|
XupsAlarmEventEntry ::= SEQUENCE {
|
|
xupsAlarmEventID Integer32,
|
|
xupsAlarmEventDateAndTime DisplayString,
|
|
xupsAlarmEventKind INTEGER,
|
|
xupsAlarmEventDescr Integer32,
|
|
xupsAlarmEventMsg DisplayString
|
|
}
|
|
|
|
xupsAlarmEventID OBJECT-TYPE
|
|
SYNTAX Integer32 (1..400)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique number that reflects the order in which the event
|
|
occurred. The oldest event in the queue will be number 1.
|
|
Subsequent events will be numbered 2, 3, 4, etc."
|
|
::= { xupsAlarmEventEntry 1 }
|
|
|
|
xupsAlarmEventDateAndTime OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..22))
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The time and date that an event occurred as recorded in the UPS
|
|
internal event queue. This string will reflect the time and
|
|
date as set in the UPS itself and will not be referenced to sysUpTime.
|
|
The format is MM/DD/YYYY:HH:MM:SS. Time is 24 hour standard."
|
|
::= { xupsAlarmEventEntry 2 }
|
|
|
|
xupsAlarmEventKind OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
occurred (1),
|
|
cleared (2),
|
|
unknown (3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Enumerated value that tells whether the event is an
|
|
occurrence of an alarm condition or a clearing of an
|
|
alarm condition."
|
|
::= { xupsAlarmEventEntry 3 }
|
|
|
|
xupsAlarmEventDescr OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"A description of the event stored in the UPS event queue.
|
|
This description will be a sixteen bit integer value
|
|
representing one of the defined alarms in the Powerware Binary
|
|
Computer Mode communication specification; for example,
|
|
a value of 0 represents the 'Inverter AC Over Voltage'
|
|
alarm (byte 1, bit 0 in the BCM Alarm Map)."
|
|
::= { xupsAlarmEventEntry 4 }
|
|
|
|
xupsAlarmEventMsg OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..80))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A text string describing each entry in the Event Log. The format of this
|
|
text message is free (not fixed) for the operator to read; good contents
|
|
would be a time & date stamp, the event type, and a description of the event."
|
|
::= { xupsAlarmEventEntry 5 }
|
|
|
|
--
|
|
-- More Well known alarm conditions.
|
|
--
|
|
xupsBreakerOpen OBJECT IDENTIFIER ::= {xupsAlarm 20}
|
|
xupsAlarmEntryAdded OBJECT IDENTIFIER ::= {xupsAlarm 21}
|
|
xupsAlarmEntryRemoved OBJECT IDENTIFIER ::= {xupsAlarm 22}
|
|
|
|
-- Same as RFC 1628 Well Known Alarms:
|
|
xupsAlarmBatteryBad OBJECT IDENTIFIER ::= {xupsAlarm 23}
|
|
xupsOutputOffAsRequested OBJECT IDENTIFIER ::= {xupsAlarm 24}
|
|
xupsDiagnosticTestFailed OBJECT IDENTIFIER ::= {xupsAlarm 25}
|
|
xupsCommunicationsLost OBJECT IDENTIFIER ::= {xupsAlarm 26}
|
|
xupsUpsShutdownPending OBJECT IDENTIFIER ::= {xupsAlarm 27}
|
|
xupsAlarmTestInProgress OBJECT IDENTIFIER ::= {xupsAlarm 28}
|
|
|
|
-- Alarm for the Ambient Temperature, when outside of lo/hi limits
|
|
xupsAmbientTempBad OBJECT IDENTIFIER ::= {xupsAlarm 29}
|
|
|
|
-- For Loss of Redundancy in parallel systems
|
|
xupsLossOfRedundancy OBJECT IDENTIFIER ::= {xupsAlarm 30}
|
|
|
|
-- More Same as RFC 1628 Well Known Alarms:
|
|
xupsAlarmTempBad OBJECT IDENTIFIER ::= {xupsAlarm 31}
|
|
xupsAlarmChargerFailed OBJECT IDENTIFIER ::= {xupsAlarm 32}
|
|
xupsAlarmFanFailure OBJECT IDENTIFIER ::= {xupsAlarm 33}
|
|
xupsAlarmFuseFailure OBJECT IDENTIFIER ::= {xupsAlarm 34}
|
|
|
|
-- A Relay, Contactor, or Breaker has failed
|
|
xupsPowerSwitchBad OBJECT IDENTIFIER ::= {xupsAlarm 35}
|
|
|
|
-- One module in a parallel or composite system has failed
|
|
xupsModuleFailure OBJECT IDENTIFIER ::= {xupsAlarm 36}
|
|
|
|
-- Two Alarms for systems with an Alternate Power Source, such as
|
|
-- Secondary utility feed (on a dual AC input UPS), generator,
|
|
-- flywheel, or fuelcell. Enabled by xupsSecondaryInputWatch.
|
|
xupsOnAlternatePowerSource OBJECT IDENTIFIER ::= {xupsAlarm 37}
|
|
xupsAltPowerNotAvailable OBJECT IDENTIFIER ::= {xupsAlarm 38}
|
|
|
|
-- Some Notice condition exists which is not covered by the other WKA
|
|
-- (like an xupsInternalFailure, but at a lower level of urgency)
|
|
xupsNoticeCondition OBJECT IDENTIFIER ::= {xupsAlarm 39}
|
|
|
|
-- Alarms for the Remote Temperature & Humidity, when outside of lo/hi limits
|
|
xupsRemoteTempBad OBJECT IDENTIFIER ::= {xupsAlarm 40}
|
|
xupsRemoteHumidityBad OBJECT IDENTIFIER ::= {xupsAlarm 41}
|
|
|
|
-- Last of the RFC1628 Well Known Alarms:
|
|
xupsAlarmOutputBad OBJECT IDENTIFIER ::= {xupsAlarm 42}
|
|
xupsAlarmAwaitingPower OBJECT IDENTIFIER ::= {xupsAlarm 43}
|
|
|
|
-- Alarm for this important UPS mode
|
|
xupsOnMaintenanceBypass OBJECT IDENTIFIER ::= {xupsAlarm 44}
|
|
|
|
-- New alarms now managed by the Network-M2 card
|
|
xupsOutputNotProtected OBJECT IDENTIFIER ::= {xupsAlarm 51}
|
|
|
|
|
|
--
|
|
-- xupsTest group:
|
|
--
|
|
|
|
xupsTestStart OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
testBattery (1),
|
|
noTestStarted (2),
|
|
testSystem (3),
|
|
testSecondarySource (4),
|
|
flashLightsTest (5),
|
|
cancelTest (6)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object initiates the requested Test.
|
|
The test types which a UPS might support are 'testBattery',
|
|
'testSystem' (a UPS General Systems test, however defined by the UPS),
|
|
'testSecondarySource' (test if the Secondary power source is good on a
|
|
dual input UPS), and
|
|
'flashLightsTest' (start a test which flashes the UPS lights, and if
|
|
available, sounds the horn to help locate the UPS).
|
|
If a UPS does not support the requested test, the set operation may
|
|
succeed but the xupsTestBatteryStatus will end up as notSupported.
|
|
When read, this object indicates the last test requested via this object,
|
|
if any; 'noTestStarted' could be the initial value.
|
|
Currently only the 'flashLightsTest' can be canceled with 'cancelTest'."
|
|
::= {xupsTest 1}
|
|
|
|
xupsTestBatteryStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown (1),
|
|
passed (2),
|
|
failed (3),
|
|
inProgress (4),
|
|
notSupported (5),
|
|
inhibited (6),
|
|
scheduled (7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reading this enumerated value gives an indication of the (last)
|
|
UPS Battery test status.
|
|
'inhibited' means that the battery test could not be run.
|
|
'scheduled' means that the battery test could not be run at the time
|
|
of request, but will be run at some later (UPS-determined) time."
|
|
::= {xupsTest 2}
|
|
|
|
xupsLastGeneralTest OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noTestStarted (2),
|
|
testSystem (3),
|
|
testSecondarySource (4),
|
|
flashLightsTest (5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the last UPS test requested via xupsTestStart or by other
|
|
non-SNMP means, other than for the testBattery (1) case.
|
|
The results of the test indicated by this object are reported in
|
|
xupsLastGeneralTestResult."
|
|
::= {xupsTest 3}
|
|
|
|
xupsLastGeneralTestResult OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown (1),
|
|
passed (2),
|
|
failed (3),
|
|
inProgress (4),
|
|
notSupported (5),
|
|
inhibited (6),
|
|
scheduled (7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reading this enumerated value gives the result of the test indicated
|
|
in xupsLastGeneralTest."
|
|
::= {xupsTest 4}
|
|
|
|
xupsTestTrap OBJECT-TYPE
|
|
SYNTAX INTEGER { startTestTrap (1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting startTestTrap to 1 will initiate a test trap
|
|
to be sent out from the agent. All other set values are invalid."
|
|
::= {xupsTest 5}
|
|
|
|
|
|
--
|
|
-- xupsControl group:
|
|
--
|
|
xupsControlOutputOffDelay OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this value to other than zero will cause the UPS
|
|
output to turn off after the number of seconds.
|
|
Setting it to 0 will cause an attempt to abort a pending
|
|
shutdown."
|
|
::= {xupsControl 1}
|
|
|
|
xupsControlOutputOnDelay OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this value to other than zero will cause the UPS
|
|
output to turn on after the number of seconds.
|
|
Setting it to 0 will cause an attempt to abort a pending
|
|
startup."
|
|
::= {xupsControl 2}
|
|
|
|
xupsControlOutputOffTrapDelay OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When xupsControlOutputOffDelay reaches this value, a trap will
|
|
be sent."
|
|
::= {xupsControl 3}
|
|
|
|
xupsControlOutputOnTrapDelay OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"When xupsControlOutputOnDelay reaches this value, a
|
|
xupsOutputOff trap will be sent."
|
|
::= {xupsControl 4}
|
|
|
|
xupsControlToBypassDelay OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this value to other than zero will cause the UPS
|
|
output to go to Bypass after the number of seconds.
|
|
If the Bypass is unavailable, this may cause the UPS
|
|
to not supply power to the load.
|
|
Setting it to 0 will cause an attempt to abort a pending
|
|
shutdown."
|
|
::= {xupsControl 5}
|
|
|
|
xupsLoadShedSecsWithRestart OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this value will cause the UPS output to turn off
|
|
after the set number of seconds, then restart (after a UPS-defined
|
|
'down time') when the utility is again available.
|
|
Unlike xupsControlOutputOffDelay, which might or might not,
|
|
this object always maps to the XCP 0x8A Load Dump & Restart command,
|
|
so the desired shutdown and restart behavior is guaranteed to happen.
|
|
Once set, this command cannot be aborted.
|
|
This is the preferred Control object to use when performing
|
|
an On Battery OS Shutdown."
|
|
::= {xupsControl 6}
|
|
|
|
xupsSwitchable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
switchable (1),
|
|
notSwitchable (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Parameter which indicates whether UPS commands received via any
|
|
communication path (aside from manual controls) are able (switchable)
|
|
or not able (notSwitchable) to control the UPS."
|
|
::= { xupsControl 7 }
|
|
|
|
--
|
|
-- xupsConfig group:
|
|
--
|
|
xupsConfigOutputVoltage OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The nominal UPS Output voltage per phase in volts."
|
|
::= {xupsConfig 1}
|
|
|
|
xupsConfigInputVoltage OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The nominal UPS Input voltage per phase in volts."
|
|
::= {xupsConfig 2}
|
|
|
|
xupsConfigOutputWatts OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The nominal UPS available real power output in watts."
|
|
::= {xupsConfig 3}
|
|
|
|
xupsConfigOutputFreq OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "0.1 Hertz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The nominal output frequency in tenths of Hz."
|
|
::= {xupsConfig 4}
|
|
|
|
xupsConfigDateAndTime OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..22))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Date and time information for the UPS. Setting this variable
|
|
will initiate a set UPS date and time to this value. Reading
|
|
this variable will return the UPS time and date. This value
|
|
is not referenced to sysUpTime. It is simply the clock value
|
|
from the UPS real time clock.
|
|
Format is as follows: MM/DD/YYYY:HH:MM:SS."
|
|
::= { xupsConfig 5 }
|
|
|
|
xupsConfigLowOutputVoltageLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Lower limit for acceptable Output Voltage, per the UPS
|
|
specifications."
|
|
::= {xupsConfig 6}
|
|
|
|
xupsConfigHighOutputVoltageLimit OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Upper limit for acceptable Output Voltage, per the UPS
|
|
specifications."
|
|
::= {xupsConfig 7}
|
|
|
|
xupsConfigInstallDate OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..16))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The date when this UPS was installed. Free text format, so the
|
|
preferred local date format may be used (MM/DD/YYYY, DD-Mon-YYYY, etc)."
|
|
::= {xupsConfig 8}
|
|
|
|
|
|
|
|
--
|
|
-- xupsTrapControl group:
|
|
--
|
|
xupsMaxTrapLevel OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none (1),
|
|
critical (2),
|
|
major (3),
|
|
minor (4),
|
|
allTraps (5)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The level of severity of traps which will be sent to the
|
|
requesting host; individual trap receivers will have
|
|
individual values for this variable. Values are:
|
|
(1) none: no traps will be sent to this host;
|
|
(2) critical: only traps for Critical alarm conditions will
|
|
be sent to this host;
|
|
(3) major: Critical and Major traps will be sent;
|
|
(4) minor: All levels of alarming traps will be sent: Critical,
|
|
Major, and Minor
|
|
(This level was added in PowerMIB v3.11)
|
|
(5) allTraps: all Traps will be sent to this host
|
|
(Critical, Major, Minor, Informational)."
|
|
::= {xupsTrapControl 1}
|
|
|
|
xupsSendTrapType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
stnd (1),
|
|
xups (2),
|
|
stndPlus (3),
|
|
xupsPlus (4),
|
|
pxg (5)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The type of traps which will be sent to the
|
|
requesting host; individual trap receivers will have
|
|
individual values for this variable. The additional
|
|
variables in types (3) and (4) are useful for determining
|
|
which UPS is the source on multi-port network adapters,
|
|
and for getting additional descriptive information.
|
|
Types (1) through (4) are all SNMP version 1 trap PDUs.
|
|
Values are:
|
|
(1) stnd: Traps as defined in the Standard UPS MIB (RFC1628)
|
|
and Generic (MIB II) traps as defined in RFC 1215.
|
|
(2) xups: xupsTrapDefined Traps as defined in the PowerMIB
|
|
and Generic (MIB II) traps as defined in RFC 1215.
|
|
(3 Deprecated) stndPlus: same as stnd plus variables from the interface
|
|
group and, where appropriate, xupsTrapMessage.
|
|
(4 Deprecated) xupsPlus: xupsTrapPortN Traps (same as xups plus
|
|
variables from the interface group) and,
|
|
for authFail, xupsTrapMessage.
|
|
(5 pxg: Traps as defined in the Power Xpert Gateway MIB
|
|
(PXG-MIB)."
|
|
::= {xupsTrapControl 2}
|
|
|
|
xupsTrapMessage OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..79))
|
|
MAX-ACCESS read-only -- actually not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A descriptive text message which may be sent with traps to
|
|
further explain the reason for the trap.
|
|
This object is not-accessible to MIB browsers, but had to be changed to
|
|
read-only to satisfy SMIv2 syntax checkers since it is included in traps."
|
|
::= {xupsTrapControl 3}
|
|
|
|
-- An Identifier for the PowerMIB traps
|
|
-- Used below in the section where the traps are defined
|
|
xupsTrapSource OBJECT IDENTIFIER ::= {xupsTrapControl 4}
|
|
|
|
xupsHeartbeatMinsInterval OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "Minutes"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"How often to send the xupstdHeartbeat trap, in units of minutes.
|
|
A setting of 0 disables the Heartbeat function."
|
|
::= {xupsTrapControl 5}
|
|
|
|
|
|
|
|
--
|
|
-- xupsRecep group:
|
|
--
|
|
-- (Note that the terms Receptacle, Outlet, and Load Group are used interchangeably
|
|
-- here and all mean "one of a group of controllable, power-switched outputs")
|
|
--
|
|
xupsNumReceptacles OBJECT-TYPE
|
|
SYNTAX Integer32 (0..64)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of independently controllable Receptacles, as described in the
|
|
xupsRecepTable."
|
|
::= {xupsRecep 1}
|
|
|
|
xupsRecepTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF XupsRecepEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of receptacle table entries. The number of entries
|
|
is given by the value of xupsNumReceptacles."
|
|
::={xupsRecep 2}
|
|
|
|
xupsRecepEntry OBJECT-TYPE
|
|
SYNTAX XupsRecepEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A receptacle table entry containing the status and
|
|
control values for one receptacle."
|
|
INDEX { xupsRecepIndex }
|
|
::= { xupsRecepTable 1 }
|
|
|
|
XupsRecepEntry ::= SEQUENCE {
|
|
xupsRecepIndex Integer32,
|
|
xupsRecepStatus INTEGER,
|
|
xupsRecepOffDelaySecs Integer32,
|
|
xupsRecepOnDelaySecs Integer32,
|
|
xupsRecepAutoOffDelay Integer32,
|
|
xupsRecepAutoOnDelay Integer32,
|
|
xupsRecepShedSecsWithRestart Integer32,
|
|
xupsRecepHourlyPowerUsage Integer32,
|
|
xupsRecepCumulativePowerUsage Integer32,
|
|
xupsRecepCumulativePowerUsageTimer Counter32
|
|
}
|
|
|
|
xupsRecepIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..64)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of the Receptacle. Serves as index for Receptacle table."
|
|
::= {xupsRecepEntry 1}
|
|
|
|
|
|
xupsRecepStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1), off(2), pendingOff(3), pendingOn(4), unknown(5),
|
|
reserved(6), failedClosed(7), failedOpen(8) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off,
|
|
4=Off w/Pending ON, 5=Unknown, 6=Reserved for future,
|
|
7=Failed in Closed position, 8=Failed in Open position."
|
|
::={xupsRecepEntry 2}
|
|
|
|
|
|
xupsRecepOffDelaySecs OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..2147483647)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Delay until the Receptacle is turned Off. Setting
|
|
this value to other than -1 will cause the UPS output to
|
|
turn off after the number of seconds (0 is immediately).
|
|
Setting it to -1 will cause an attempt to abort a pending shutdown.
|
|
When this object is set while the UPS is On Battery, it is not necessary
|
|
to set xupsRecepOnDelaySecs, since the outlet will turn back on
|
|
automatically when power is available again."
|
|
::= {xupsRecepEntry 3}
|
|
|
|
xupsRecepOnDelaySecs OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..2147483647)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Delay until the Receptacle is turned On. Setting
|
|
this value to other than -1 will cause the UPS output to
|
|
turn on after the number of seconds (0 is immediately).
|
|
Setting it to -1 will cause an attempt to abort a pending restart."
|
|
::={xupsRecepEntry 4}
|
|
|
|
|
|
xupsRecepAutoOffDelay OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..32767)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delay after going On Battery until the Receptacle is
|
|
automatically turned Off. A value of -1 means that this Output should
|
|
never be turned Off automatically, but must be turned Off only by command.
|
|
Values from 0 to 30 are valid, but probably innappropriate.
|
|
The AutoOffDelay can be used to prioritize loads in the event of a prolonged
|
|
power outage; less critical loads will turn off earlier to extend battery
|
|
time for the more critical loads. If the utility power is restored before the
|
|
AutoOff delay counts down to 0 on an outlet, that outlet will not turn Off."
|
|
::= {xupsRecepEntry 5}
|
|
|
|
xupsRecepAutoOnDelay OBJECT-TYPE
|
|
SYNTAX Integer32 (-1..32767)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Seconds delay after the Outlet is signaled to turn On before the Output is
|
|
Automatically turned ON. A value of -1 means that this Output should never
|
|
be turned On automatically, but only when specifically commanded to do so.
|
|
A value of 0 means that the Receptacle should come On immediately
|
|
at power-up or for an On command."
|
|
::= {xupsRecepEntry 6}
|
|
|
|
-- xupsRecepAutoOnDelay has three purposes:
|
|
-- 1. To coordinate the automatic startup of various outlets, when the normal
|
|
-- auto-sequencing of 1 second per outlet is not adequate. For example, they may
|
|
-- be used to power up hard disk arrays before CPU units are started.
|
|
-- 2. To force additional 'Down Time' during xupsRecepOffDelaySecs commands, for
|
|
-- equipment to be reset, when the standard 'Down Time' is not long enough.
|
|
-- 3. For the -1 value, to ensure that loads won't be powered until commanded,
|
|
-- following power-up or a xupsRecepOffDelaySecs command.
|
|
|
|
xupsRecepShedSecsWithRestart OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this value will cause the UPS output to turn off
|
|
after the set number of seconds, then restart (after a UPS-defined
|
|
'down time') when the utility is again available.
|
|
Unlike xupsRecepOffDelaySecs, which might or might not,
|
|
this object always maps to the XCP 0x8A Load Dump & Restart command,
|
|
so the desired shutdown and restart behavior is guaranteed to happen.
|
|
Once set, this command cannot be aborted."
|
|
::= {xupsRecepEntry 7}
|
|
|
|
xupsRecepHourlyPowerUsage OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "Wh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Units are Watt-hours.This is the energy consumed during the last hour."
|
|
::= { xupsRecepEntry 8 }
|
|
|
|
xupsRecepCumulativePowerUsage OBJECT-TYPE
|
|
SYNTAX Integer32 (0..2147483647)
|
|
UNITS "Wh"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Units are Watt-hours.This is the energy consumed since the last reset.
|
|
This object is writable so that it can be reset to 0.
|
|
When it is written to 0, the xupsRecepCumulativePowerUsageTimer will be reset to 0 as well."
|
|
::= { xupsRecepEntry 9 }
|
|
|
|
xupsRecepCumulativePowerUsageTimer OBJECT-TYPE
|
|
SYNTAX Counter32
|
|
UNITS "Seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time in seconds since the cumulative power usage was last reset."
|
|
::= { xupsRecepEntry 10 }
|
|
|
|
|
|
--
|
|
-- xupsTopology group:
|
|
--
|
|
xupsTopologyType OBJECT-TYPE
|
|
SYNTAX Integer32 (0..32767)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value which denotes the type of UPS by its power topology. Values are the
|
|
same as those described in the XCP Topology block's Overall Topology field."
|
|
::= {xupsTopology 1}
|
|
|
|
xupsTopoMachineCode OBJECT-TYPE
|
|
SYNTAX Integer32 (0..32767)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ID Value which denotes the Powerware model of the UPS for software.
|
|
Values are the same as those described in the XCP Configuration
|
|
block's Machine Code field."
|
|
::= {xupsTopology 2}
|
|
|
|
xupsTopoUnitNumber OBJECT-TYPE
|
|
SYNTAX Integer32 (0..64)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Identifies which unit and what type of data is being reported.
|
|
A value of 0 means that this MIB information comes from the top-level system
|
|
view (eg, manifold module or system bypass cabinet reporting total system
|
|
output). Standalone units also use a value of 0, since they are the 'full
|
|
system' view.
|
|
A value of 1 or higher indicates the number of the module in the system
|
|
which is reporting only its own data in the PowerMIB objects."
|
|
::= {xupsTopology 3}
|
|
|
|
xupsTopoPowerStrategy OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
highAlert(1), standard(2), enableHighEfficiency(3),
|
|
immediateHighEfficiency(4) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Value which denotes which Power Strategy is currently set for the UPS.
|
|
The values are:
|
|
highAlert(1) - The UPS shall optimize its operating state to maximize its
|
|
power-protection levels. This mode will be held for at most 24 hours.
|
|
standard(2) - Balanced, normal power protection strategy. UPS will not enter
|
|
HE operating mode from this setting.
|
|
enableHighEfficiency(3) - The UPS is enabled to enter HE operating mode to
|
|
optimize its operating state to maximize its efficiency, when
|
|
conditions change to permit it (as determined by the UPS).
|
|
forceHighEfficiency(4) - If this value is permitted to be Set for this UPS,
|
|
and if conditions permit, requires the UPS to enter High Efficiency
|
|
mode now, without delay (for as long as utility conditions permit).
|
|
After successfully set to forceHighEfficiency(4),
|
|
xupsTopoPowerStrategy changes to value enableHighEfficiency(3).
|
|
xupsOutputSource will indicate if the UPS status is actually operating in
|
|
High Efficiency mode."
|
|
::= {xupsTopology 4}
|
|
|
|
|
|
--
|
|
-- xupsAgent group:
|
|
--
|
|
xupsAgentManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The card agent Manufacturer Name (e.g. Eaton Corporation)."
|
|
::= { xupsAgent 1}
|
|
|
|
xupsAgentModel OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The card agent model"
|
|
::= {xupsAgent 2}
|
|
|
|
xupsAgentSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The agent firmware version."
|
|
::= {xupsAgent 3}
|
|
|
|
xupsAgentPartNumber OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..31))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The card agent catalog part number."
|
|
::= { xupsAgent 4 }
|
|
|
|
xupsAgentSerialNumber OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(1..31))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The card agent catalog serial number."
|
|
::= { xupsAgent 5 }
|
|
|
|
|
|
-- *************************************************************************
|
|
-- *************************************************************************
|
|
|
|
--
|
|
-- Traps (xupst)
|
|
--
|
|
-- 1) Eaton's traps have been defined in this MIB for three different sources.
|
|
-- The trap definitions for the three sources are very similar,
|
|
-- and use the same alarms as their triggers; their names are prefaced
|
|
-- by xupstb, xupstd, and xupstp to distinguish the three types
|
|
-- However, the products that the "Basic" and "Port Defined" trap types were
|
|
-- created for have been obsoleted, so the only trap types in active use
|
|
-- are the "Defined" (xupstd) traps listed below
|
|
-- The Obsolete types have been moved to file XUPS_Obsolete.mib
|
|
--
|
|
-- a) OBSOLETE - Basic Agents for which the trap variables have not been
|
|
-- defined, though trap variables are included with the trap PDU
|
|
-- xupsNull OBJECT IDENTIFIER ::= { xupsMIB 0 }
|
|
-- xupsTrapBasic OBJECT IDENTIFIER ::= { xupsNull 0 }
|
|
--
|
|
|
|
-- b) Agents with exactly Defined trap variables, which may be
|
|
-- used as input to trap response macros on management stations
|
|
-- This trap type is selected by setting xupsSendTrapType to xups(2)
|
|
xupsTrapDefined OBJECT IDENTIFIER ::= {xupsTrapSource 1}
|
|
-- Following the recommendations for coexistence between v1 traps
|
|
-- and v2 notifications, define the snmpTrapOID base with a 0
|
|
xupsTrapOidDefined OBJECT IDENTIFIER ::= { xupsTrapDefined 0 }
|
|
|
|
--
|
|
-- c) OBSOLETE - Agents with Defined traps including ifIndex and ifDescr,
|
|
-- which can be used to determine which UPS of a multi-port
|
|
-- agent (eg, Eaton Network SNMP Adapter) sent the trap
|
|
-- This trap type was selected by setting xupsSendTrapType to xupsPlus(4)
|
|
-- xupsTrapPortN OBJECT IDENTIFIER ::= {xupsTrapSource 2}
|
|
--
|
|
-- 2) Trap Severity Level is given as a comment to indicate which
|
|
-- xupsMaxTrapLevel will result in this trap being sent;
|
|
-- levels are (in order): Critical, Major, Minor, Informational
|
|
--
|
|
|
|
|
|
-- ****************************************************************************
|
|
-- ****************************************************************************
|
|
--
|
|
-- Traps from xupsTrapDefined source (xupstd):
|
|
--
|
|
|
|
xupstdControlOff NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS output power will turn off in a number of
|
|
seconds equal to upsControlOutputOffTrapDelay."
|
|
--#SEVERITY CRITICAL
|
|
::= { xupsTrapOidDefined 1 }
|
|
|
|
xupstdControlOn NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS output power will turn on in a number of
|
|
seconds equal to upsControlOutputOnTrapDelay."
|
|
--#SEVERITY INFORMATIONAL
|
|
::= { xupsTrapOidDefined 2 }
|
|
|
|
xupstdOnBattery NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS has no AC input power and is running on
|
|
battery."
|
|
--#SEVERITY MAJOR
|
|
::= { xupsTrapOidDefined 3 }
|
|
|
|
xupstdLowBattery NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS batteries are low. Tied to low battery
|
|
alarm condition."
|
|
--#SEVERITY CRITICAL
|
|
::= { xupsTrapOidDefined 4 }
|
|
|
|
xupstdUtilityPowerRestored NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input power has been restored after running on battery."
|
|
--#SEVERITY INFORMATIONAL
|
|
::= { xupsTrapOidDefined 5 }
|
|
|
|
xupstdReturnFromLowBattery NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery has recovered from a low battery condition."
|
|
--#SEVERITY INFORMATIONAL
|
|
::= { xupsTrapOidDefined 6 }
|
|
|
|
xupstdOutputOverload NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ups has sensed an overload of greater than
|
|
106 percent. Tied to the 106% overload alarm."
|
|
--#SEVERITY MINOR
|
|
::= { xupsTrapOidDefined 7 }
|
|
|
|
xupstdInternalFailure NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Some component of the ups - rectifier, inverter,
|
|
control panel has failed. Tied to alarms indi-
|
|
cating failure."
|
|
--#SEVERITY CRITICAL
|
|
::= { xupsTrapOidDefined 8 }
|
|
|
|
xupstdBatteryDischarged NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Battery Totally Discharged Alarm has occurred."
|
|
--#SEVERITY CRITICAL
|
|
::= { xupsTrapOidDefined 9 }
|
|
|
|
xupstdInverterFailure NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ups inverter is unavailable or malfunctioning due to an internal failure."
|
|
--#SEVERITY CRITICAL
|
|
::= { xupsTrapOidDefined 10 }
|
|
|
|
xupstdOnBypass NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ups has gone on bypass for some reason."
|
|
--#SEVERITY CRITICAL
|
|
::= { xupsTrapOidDefined 11 }
|
|
|
|
xupstdBypassNotAvailable NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ups bypass is unavailable"
|
|
--#SEVERITY MAJOR
|
|
::= { xupsTrapOidDefined 12 }
|
|
|
|
xupstdOutputOff NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ups output is switched off."
|
|
--#SEVERITY CRITICAL
|
|
::= { xupsTrapOidDefined 13 }
|
|
|
|
xupstdInputFailure NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ups input power is incorrect in voltage,
|
|
frequency, or phase rotation."
|
|
--#SEVERITY MINOR
|
|
::= { xupsTrapOidDefined 14 }
|
|
|
|
xupstdBuildingAlarm NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One of the defined building alarms has occurred."
|
|
--#SEVERITY MAJOR
|
|
::= { xupsTrapOidDefined 15 }
|
|
|
|
xupstdShutdownImminent NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ups shutdown imminent alarm has occurred."
|
|
--#SEVERITY CRITICAL
|
|
::= { xupsTrapOidDefined 16 }
|
|
|
|
xupstdOnInverter NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ups is returned to utility power running the inverter
|
|
after either a transfer to bypass or a run on battery."
|
|
--#SEVERITY INFORMATIONAL
|
|
::= { xupsTrapOidDefined 17 }
|
|
|
|
xupstdBreakerOpen NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One of the UPS breakers or contactors has been opened."
|
|
--#SEVERITY MAJOR
|
|
::= { xupsTrapOidDefined 20 }
|
|
|
|
xupstdAlarmEntryAdded NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An alarm not defined in the xups Well Known Alarms
|
|
(eg, an alarm defined in RFC1628)
|
|
has been added to the Alarm Table."
|
|
--#SEVERITY MAJOR
|
|
::= { xupsTrapOidDefined 21 }
|
|
|
|
xupstdAlarmEntryRemoved NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An alarm not defined in the xups Well Known Alarms
|
|
has been removed from the Alarm Table."
|
|
--#SEVERITY INFORMATIONAL
|
|
::= { xupsTrapOidDefined 22 }
|
|
|
|
xupstdAlarmBatteryBad NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more batteries have been determined to require replacement."
|
|
--#SEVERITY MAJOR
|
|
::= { xupsTrapOidDefined 23 }
|
|
|
|
xupstdOutputOffAsRequested NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS has shutdown as requested, i.e., the output is off."
|
|
--#SEVERITY INFORMATIONAL
|
|
::= { xupsTrapOidDefined 24 }
|
|
|
|
xupstdDiagnosticTestFailed NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The result of the last diagnostic test indicates a failure."
|
|
--#SEVERITY MINOR
|
|
::= { xupsTrapOidDefined 25 }
|
|
|
|
xupstdCommunicationsLost NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A problem has been encountered in the communications
|
|
between the agent and the UPS."
|
|
--#SEVERITY MAJOR
|
|
::= { xupsTrapOidDefined 26 }
|
|
|
|
xupstdUpsShutdownPending NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An xupsControlOutputOffDelay countdown is underway."
|
|
--#SEVERITY MAJOR
|
|
::= { xupsTrapOidDefined 27 }
|
|
|
|
xupstdAlarmTestInProgress NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A test is in progress, as initiated and indicated by the xupsTest Group.
|
|
When the test is complete, one of the following traps will be sent:
|
|
- xupstdDiagnosticTestFailed if the test fails,
|
|
- xupstdDiagnosticTestPassed on success, or
|
|
- xupstdAlarmEntryRemoved in other cases (e.g., Test Canceled)."
|
|
--#SEVERITY INFORMATIONAL
|
|
::= { xupsTrapOidDefined 28 }
|
|
|
|
-- Provide additional information with the AmbientTemp trap
|
|
xupstdAmbientTempBad NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
|
xupsEnvAmbientTemp, xupsEnvAmbientLowerLimit,
|
|
xupsEnvAmbientUpperLimit }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ambient temperature, xupsEnvAmbientTemp, has fallen below
|
|
the set lower limit, xupsEnvAmbientLowerLimit, or has risen above
|
|
the set upper limit, xupsEnvAmbientUpperLimit."
|
|
--#SEVERITY MAJOR
|
|
::= { xupsTrapOidDefined 29 }
|
|
|
|
-- Added to support the ConnectUPS Web/SNMP card's ability to monitor contact(s)
|
|
xupstdContactActiveNotice NOTIFICATION-TYPE
|
|
OBJECTS { xupsContactIndex, xupsContactType, xupsContactState, xupsContactDescr }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Contact indicated by xupsContactIndex is in its Active state.
|
|
The following are the situations that generate this trap:
|
|
For xupsContactType: and xupsContactState:
|
|
normallyOpen(1) and closedWithNotice(4)
|
|
normallyClosed(2) and openWithNotice(3)
|
|
anyChange(3) and openWithNotice(3) or closedWithNotice(4)"
|
|
--#SEVERITY MAJOR
|
|
::= { xupsTrapOidDefined 30 }
|
|
|
|
xupstdContactInactiveNotice NOTIFICATION-TYPE
|
|
OBJECTS { xupsContactIndex, xupsContactType, xupsContactState, xupsContactDescr }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Contact indicated by xupsContactIndex has changed to its Inactive state."
|
|
--#SEVERITY INFORMATIONAL
|
|
::= { xupsTrapOidDefined 31 }
|
|
|
|
|
|
xupstdLossOfRedundancy NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A parallel UPS system is no longer operating in N+1 redundant mode;
|
|
this may be due to module failure or removal, or due to overloading."
|
|
--#SEVERITY MINOR
|
|
::= { xupsTrapOidDefined 32 }
|
|
|
|
xupstdAlarmTempBad NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An internal temperature is out of tolerance."
|
|
--#SEVERITY MAJOR
|
|
::= { xupsTrapOidDefined 33 }
|
|
|
|
xupstdAlarmChargerFailed NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An uncorrected problem has been detected within the UPS charger subsystem."
|
|
--#SEVERITY MAJOR
|
|
::= { xupsTrapOidDefined 34 }
|
|
|
|
xupstdAlarmFanFailure NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The failure of one or more fans in the UPS has been detected."
|
|
--#SEVERITY MAJOR
|
|
::= { xupsTrapOidDefined 35 }
|
|
|
|
xupstdAlarmFuseFailure NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The failure of one or more fuses has been detected."
|
|
--#SEVERITY CRITICAL
|
|
::= { xupsTrapOidDefined 36 }
|
|
|
|
xupstdPowerSwitchBad NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A Relay, Contactor, or Breaker has failed."
|
|
--#SEVERITY CRITICAL
|
|
::= { xupsTrapOidDefined 37 }
|
|
|
|
xupstdModuleFailure NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One module in a parallel or composite system has failed."
|
|
--#SEVERITY MAJOR
|
|
::= { xupsTrapOidDefined 38 }
|
|
|
|
-- xupsInputSource added to this trap's var list
|
|
xupstdOnAlternatePowerSource NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage, xupsInputSource }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system is being powered by its Alternate Power Source, such as a
|
|
Secondary utility feed (on a dual AC input UPS), generator, flywheel,
|
|
or fuel cell."
|
|
--#SEVERITY MINOR
|
|
::= { xupsTrapOidDefined 39 }
|
|
|
|
xupstdAltPowerNotAvailable NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"On systems with a separate alternate power source (eg, dual AC inputs),
|
|
that alternate power source is currently not available. This could be
|
|
a problem if the primary power source (eg, utility) fails for a period
|
|
of time longer than that for which the internal batteries can supply power."
|
|
--#SEVERITY MINOR
|
|
::= { xupsTrapOidDefined 40 }
|
|
|
|
xupstdNoticeCondition NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Some Notice condition exists which is not covered by the other traps.
|
|
This is like an xupstdInternalFailure, but at a lower severity level."
|
|
--#SEVERITY MINOR
|
|
::= { xupsTrapOidDefined 41 }
|
|
|
|
|
|
-- Added to provide additional information with the RemoteTemp and RemoteHumidity
|
|
xupstdRemoteTempBad NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
|
xupsEnvRemoteTemp, xupsEnvRemoteTempLowerLimit,
|
|
xupsEnvRemoteTempUpperLimit }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The remote temperature, xupsEnvRemoteTemp, has fallen below
|
|
the set lower limit, xupsEnvRemoteTempLowerLimit, or has risen above
|
|
the set upper limit, xupsEnvRemoteTempUpperLimit."
|
|
--#SEVERITY MAJOR
|
|
::= { xupsTrapOidDefined 42 }
|
|
|
|
xupstdRemoteHumidityBad NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage,
|
|
xupsEnvRemoteHumidity, xupsEnvRemoteHumidityLowerLimit,
|
|
xupsEnvRemoteHumidityUpperLimit }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The remote temperature, xupsEnvRemoteHumidity, has fallen below
|
|
the set lower limit, xupsEnvRemoteHumidityLowerLimit, or has risen above
|
|
the set upper limit, xupsEnvRemoteHumidityUpperLimit."
|
|
--#SEVERITY MINOR
|
|
::= { xupsTrapOidDefined 43 }
|
|
|
|
|
|
xupstdHeartbeat NOTIFICATION-TYPE
|
|
OBJECTS { xupsInputSource, xupsOutputSource, xupsAlarms }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A periodic status trap message. It is sent at an interval
|
|
set by object xupsHeartbeatMinsInterval.
|
|
The included variables provide a brief statement of the UPS status."
|
|
--#SEVERITY INFORMATIONAL
|
|
::= { xupsTrapOidDefined 44 }
|
|
|
|
xupstdDiagnosticTestPassed NOTIFICATION-TYPE
|
|
OBJECTS { xupsTestBatteryStatus, xupsLastGeneralTest, xupsLastGeneralTestResult }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A diagnostic test just completed, and its result is Passed.
|
|
The included variables provide additional information on the test."
|
|
--#SEVERITY INFORMATIONAL
|
|
::= { xupsTrapOidDefined 45 }
|
|
|
|
xupstdOutputBad NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output condition (other than OutputOverload) is out of tolerance."
|
|
--#SEVERITY CRITICAL
|
|
::= { xupsTrapOidDefined 46 }
|
|
|
|
xupstdAwaitingPower NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS output is off and the UPS is awaiting the return of input power."
|
|
--#SEVERITY MINOR
|
|
::= { xupsTrapOidDefined 47 }
|
|
|
|
xupstdOnMaintenanceBypass NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS has been placed on Maintenance / Manual Bypass by an operator."
|
|
--#SEVERITY MAJOR
|
|
::= { xupsTrapOidDefined 48 }
|
|
|
|
xupstdCommEstablished NOTIFICATION-TYPE
|
|
OBJECTS { xupsIdentModel, xupsOutputSource }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This trap is sent when the SNMP agent first establishes a communication
|
|
link with the UPS.
|
|
The included variables provide identification and UPS status information."
|
|
--#SEVERITY INFORMATIONAL
|
|
::= { xupsTrapOidDefined 49 }
|
|
|
|
xupstdAgentDown NOTIFICATION-TYPE
|
|
-- OBJECTS { (none) }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This trap is sent when the SNMP agent is exiting or closing down gracefully.
|
|
This may be triggered by a signal from the OS to stop this process. In many
|
|
implementations, it will be followed quickly by a restart of this vital process."
|
|
--#SEVERITY MINOR
|
|
::= { xupsTrapOidDefined 50 }
|
|
|
|
-- New traps now managed by the Network-M2 card
|
|
xupstdOutputNotProtected NOTIFICATION-TYPE
|
|
OBJECTS { xupsAlarmID, xupsAlarmDescr, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ups output is not protectet for any reason in the UPS."
|
|
--#SEVERITY CRITICAL
|
|
::= { xupsTrapOidDefined 51 }
|
|
|
|
xupstdTestTrap NOTIFICATION-TYPE
|
|
OBJECTS { sysName, xupsTrapMessage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This trap is sent to the trap receivers to check proper reception of traps."
|
|
--#SEVERITY INFORMATIONAL
|
|
::= { xupsTrapOidDefined 100 }
|
|
|
|
--
|
|
-- Conformance-related definitions
|
|
-- (Defined mostly to satisfy the MIB checkers.)
|
|
--
|
|
xupsConformance OBJECT IDENTIFIER ::= { xupsMIB 100 }
|
|
|
|
xupsIdentFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsIdentManufacturer, xupsIdentModel,
|
|
xupsIdentSoftwareVersion, xupsIdentOemCode,
|
|
xupsIdentPartNumber, xupsIdentSerialNumber }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsIdent subgroup objects."
|
|
::= { xupsConformance 2 }
|
|
|
|
xupsBatteryFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsBatTimeRemaining, xupsBatVoltage, xupsBatCurrent,
|
|
xupsBatCapacity, xupsBatteryAbmStatus, xupsBatteryLastReplacedDate,
|
|
xupsBatteryFailure, xupsBatteryNotPresent, xupsBatteryAged, xupsBatteryLowCapacity }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsBattery subgroup objects."
|
|
::= { xupsConformance 3 }
|
|
|
|
xupsInputFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsInputFrequency, xupsInputLineBads, xupsInputNumPhases,
|
|
xupsInputSource, xupsDualInputStatus, xupsSecondaryInputWatch, xupsInputStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsInput subgroup objects."
|
|
::= { xupsConformance 4 }
|
|
|
|
xupsInputTableFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsInputPhase, xupsInputVoltage, xupsInputCurrent, xupsInputWatts,
|
|
xupsInputId, xupsInputName, xupsInputCurrentHighPrecision, xupsInputVoltagePhaseToPhase }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsInputTable subgroup objects."
|
|
::= { xupsConformance 5 }
|
|
|
|
xupsOutputFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsOutputLoad, xupsOutputFrequency, xupsOutputNumPhases, xupsOutputSource,
|
|
xupsOutputHourlyPowerUsage, xupsOutputCumulativePowerUsage, xupsOutputCumulativePowerUsageTimer, xupsOutputStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsOutput subgroup objects."
|
|
::= { xupsConformance 6 }
|
|
|
|
xupsOutputTableFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsOutputPhase, xupsOutputVoltage, xupsOutputCurrent, xupsOutputWatts,
|
|
xupsOutputId, xupsOutputName, xupsOutputCurrentHighPrecision, xupsOutputPercentLoad, xupsOutputVA, xupsOutputVoltagePhaseToPhase }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsOutputTable subgroup objects."
|
|
::= { xupsConformance 7 }
|
|
|
|
xupsBypassFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsBypassFrequency, xupsBypassNumPhases, xupsBypassPhase, xupsBypassVoltage, xupsBypassVoltagePhaseToPhase }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsBypass subgroup objects."
|
|
::= { xupsConformance 8 }
|
|
|
|
xupsEnvironmentFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsEnvAmbientTemp, xupsEnvAmbientLowerLimit,
|
|
xupsEnvAmbientUpperLimit, xupsEnvAmbientHumidity }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsEnvironment subgroup objects."
|
|
::= { xupsConformance 9 }
|
|
|
|
xupsAlarmFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsAlarms, xupsAlarmID, xupsAlarmDescr, xupsAlarmTime }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsAlarm subgroup objects."
|
|
::= { xupsConformance 10 }
|
|
|
|
xupsAlarmEventsFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsAlarmNumEvents, xupsAlarmEventMsg }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of Alarm/Event history subgroup objects."
|
|
::= { xupsConformance 11 }
|
|
|
|
xupsTestFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsTestStart, xupsTestBatteryStatus, xupsLastGeneralTest,
|
|
xupsLastGeneralTestResult, xupsTestTrap }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsTest subgroup objects."
|
|
::= { xupsConformance 12 }
|
|
|
|
xupsControlFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsControlOutputOffDelay, xupsControlOutputOnDelay,
|
|
xupsControlOutputOffTrapDelay, xupsControlToBypassDelay,
|
|
xupsLoadShedSecsWithRestart, xupsSwitchable }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsControl subgroup objects."
|
|
::= { xupsConformance 13 }
|
|
|
|
xupsConfigFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsConfigOutputVoltage, xupsConfigInputVoltage, xupsConfigOutputWatts,
|
|
xupsConfigOutputFreq, xupsConfigDateAndTime, xupsConfigLowOutputVoltageLimit,
|
|
xupsConfigHighOutputVoltageLimit, xupsConfigInstallDate }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsConfig subgroup objects."
|
|
::= { xupsConformance 14 }
|
|
|
|
xupsTrapControlFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsMaxTrapLevel, xupsSendTrapType, xupsTrapMessage,
|
|
xupsHeartbeatMinsInterval }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsTrapControl subgroup objects."
|
|
::= { xupsConformance 15 }
|
|
|
|
xupsRecepFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsNumReceptacles, xupsRecepIndex, xupsRecepStatus,
|
|
xupsRecepOffDelaySecs, xupsRecepOnDelaySecs,
|
|
xupsRecepAutoOffDelay, xupsRecepAutoOnDelay, xupsRecepShedSecsWithRestart,
|
|
xupsRecepHourlyPowerUsage, xupsRecepCumulativePowerUsage, xupsRecepCumulativePowerUsageTimer }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsRecep subgroup objects."
|
|
::= { xupsConformance 16 }
|
|
|
|
xupsTopologyFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsTopologyType, xupsTopoMachineCode,
|
|
xupsTopoUnitNumber, xupsTopoPowerStrategy }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsTopology subgroup objects."
|
|
::= { xupsConformance 17 }
|
|
|
|
xupstdNotifyGroup NOTIFICATION-GROUP
|
|
NOTIFICATIONS { xupstdControlOff, xupstdControlOn, xupstdOnBattery, xupstdLowBattery,
|
|
xupstdUtilityPowerRestored, xupstdReturnFromLowBattery,
|
|
xupstdOutputOverload, xupstdInternalFailure, xupstdBatteryDischarged,
|
|
xupstdInverterFailure, xupstdOnBypass, xupstdBypassNotAvailable,
|
|
xupstdOutputOff, xupstdInputFailure, xupstdBuildingAlarm,
|
|
xupstdShutdownImminent, xupstdOnInverter, xupstdBreakerOpen,
|
|
xupstdAlarmEntryAdded, xupstdAlarmEntryRemoved, xupstdAlarmBatteryBad,
|
|
xupstdOutputOffAsRequested, xupstdDiagnosticTestFailed,
|
|
xupstdCommunicationsLost, xupstdUpsShutdownPending, xupstdAlarmTempBad,
|
|
xupstdAlarmTestInProgress, xupstdAmbientTempBad, xupstdLossOfRedundancy,
|
|
xupstdAlarmChargerFailed, xupstdAlarmFanFailure, xupstdAlarmFuseFailure,
|
|
xupstdPowerSwitchBad, xupstdModuleFailure, xupstdOnAlternatePowerSource,
|
|
xupstdAltPowerNotAvailable, xupstdNoticeCondition, xupstdHeartbeat,
|
|
xupstdDiagnosticTestPassed, xupstdOutputBad, xupstdAwaitingPower,
|
|
xupstdOnMaintenanceBypass, xupstdCommEstablished, xupstdAgentDown,
|
|
xupstdOutputNotProtected, xupstdTestTrap }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Alarm and Event notifications from the xupsTrapDefined source (xupstd)."
|
|
::= { xupsConformance 18 }
|
|
|
|
xupstdEMPNotifyGroup NOTIFICATION-GROUP
|
|
NOTIFICATIONS { xupstdContactActiveNotice, xupstdContactInactiveNotice,
|
|
xupstdRemoteTempBad, xupstdRemoteHumidityBad }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The EMP's Alarm and Event notifications from the xupsTrapDefined source (xupstd)."
|
|
::= { xupsConformance 19 }
|
|
|
|
|
|
xupsMibFullCompliance MODULE-COMPLIANCE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A compliance statement for all of everything in this MIB."
|
|
MODULE -- this module
|
|
MANDATORY-GROUPS { xupsIdentFullGroup, xupsBatteryFullGroup, xupsInputFullGroup,
|
|
xupsInputTableFullGroup, xupsOutputFullGroup, xupsOutputTableFullGroup,
|
|
xupsBypassFullGroup, xupsEnvironmentFullGroup, xupsAlarmFullGroup,
|
|
xupsAlarmEventsFullGroup, xupsTestFullGroup, xupsControlFullGroup,
|
|
xupsConfigFullGroup, xupsTrapControlFullGroup, xupsRecepFullGroup,
|
|
xupsTopologyFullGroup, xupstdNotifyGroup, xupstdEMPNotifyGroup,
|
|
xupsBypassTableFullGroup, xupsInputTotalFullGroup, xupsOutputTotalFullGroup,
|
|
xupsBypassTotalFullGroup }
|
|
::= { xupsConformance 20 }
|
|
|
|
xupsDeprecatedGroup OBJECT-GROUP
|
|
OBJECTS { xupsAlarmEventDateAndTime, xupsAlarmEventKind,
|
|
xupsAlarmEventDescr, xupsControlOutputOnTrapDelay }
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"Contains objects which are now deprecated."
|
|
::= { xupsConformance 21 }
|
|
|
|
xupsBypassTableFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsBypassId, xupsBypassName, xupsBypassCurrentHighPrecision, xupsBypassWatts}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsBypassTable subgroup objects."
|
|
::= { xupsConformance 22 }
|
|
|
|
xupsInputTotalFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsInputAverageVoltage, xupsInputTotalCurrent, xupsInputTotalWatts,
|
|
xupsInputTotalVA, xupsInputAveragePowerFactor }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsInputTotal subgroup objects."
|
|
::= { xupsConformance 23 }
|
|
|
|
xupsOutputTotalFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsOutputAverageVoltage, xupsOutputTotalCurrent, xupsOutputTotalWatts,
|
|
xupsOutputTotalVA, xupsOutputAveragePowerFactor }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsOutputTotal subgroup objects."
|
|
::= { xupsConformance 24 }
|
|
|
|
xupsBypassTotalFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsBypassAverageVoltage, xupsBypassTotalCurrent, xupsBypassTotalWatts,
|
|
xupsBypassTotalVA, xupsBypassAveragePowerFactor }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsOutputTotal subgroup objects."
|
|
::= { xupsConformance 25 }
|
|
|
|
xupsAgentFullGroup OBJECT-GROUP
|
|
OBJECTS { xupsAgentManufacturer, xupsAgentModel,
|
|
xupsAgentSoftwareVersion, xupsAgentPartNumber, xupsAgentSerialNumber }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Full set of xupsAgent subgroup objects."
|
|
::= { xupsConformance 26 }
|
|
|
|
END
|
|
|