groups:
- name: ups.rules
rules:
- alert: UpsOutputSourceChanged
expr: upsOutputSource != 3
for: 0m
labels:
severity: critical
annotations:
summary: >-
Source d'alimentation changée
- alert: UpsBatteryStatus
expr: upsBatteryStatus == 3
for: 0m
labels:
severity: warning
annotations:
summary: >-
État de la batterie faible
- alert: UpsBatteryStatus
expr: upsBatteryStatus == 4
for: 0m
labels:
severity: critical
annotations:
summary: >-
État de la batterie critique
- alert: UpsHighLoad
expr: upsOutputPercentLoad > 70
for: 3m
labels:
severity: critical
annotations:
summary: >-
Charge de {{ raw('$value | printf "%.1f"') }}%
- alert: UpsWrongInputVoltage
expr: (upsInputVoltage < 210) or (upsInputVoltage > 250)
for: 5m
labels:
severity: warning
annotations:
summary: >-
Tension d'entrée de {{ raw('$value') }}V
- alert: UpsWrongOutputVoltage
expr: >-
abs(upsInputVoltage - avg_over_time(upsOutputVoltage[1d]))
< 3 * stddev_over_time(upsOutputVoltage[1d])
for: 5m
labels:
severity: warning
annotations:
summary: >-
Tension de sortie de {{ raw('$value') }}V
- alert: UpsTimeRemaining
expr: upsEstimatedMinutesRemaining < 8
for: 0m
labels:
severity: warning
annotations:
summary: >-
Autonomie restante de {{ raw('$value') }} min
- alert: UpsTimeRemaining
expr: upsEstimatedMinutesRemaining < 5
for: 0m
labels:
severity: critical
annotations:
summary: >-
Autonomie restante de {{ raw('$value') }} min
...